Features

  • Programmable bus voltages
  • Programmable bus frequencies
  • Programmable phase angle difference between two buses
  • Dead bus Active/Inhibit feature
  • History of 5 latest relay closing details
  • Self Supervision facility

Principle of Operation:

JNF 060 monitors voltage, frequency and phase angle difference of both the buses. If “dead bus” feature is Inhibit and If the voltage, frequency and the phase angle differences are within the pre-set limits, then the N/O contacts of the relay operates indicating synchronization of the buses else the relay does not operate.

If “dead bus” feature is Active and if the status of one of the buses (bus-1) is programmed as “dead bus” and the other (bus-2) is considered normal, Then, the relay operates if the voltage on bus-2 is greater than 80% of the rated voltage and the voltage on bus-1 is lesser than a programmable value (30%-80% of the rated voltage).

Output relay can be operated either in continuous mode or pulse mode. In continuous mode, the relay N/O contacts operate after a programmable delay and will remain in that condition until either a synchro check fails or h/w or power on reset occurs. In the pulse mode, the relay N/O contacts operate for a short while and gets released after a fixed delay of 150msec.

Application:

JNF 060 is used in power systems in order to prevent interconnection of badly synchronized supplies. Synchro check relay is used in series with a breaker closing circuit and automates the operation of synchronizing two buses.

20 in stock

Description

Ratings

Voltage rating (Un ) 110V AC 63.5V AC
Frequency rating 50Hz
Aux. Supply
  1. 20 to 60V DC
  2. 75 to 150V AC / DC
  3. 175 to 300V DC
  4. 185 to 250V AC

Settings:

Min voltage 1 10 to 100% of Un in steps of 1%
Min voltage 2 10 to 100% of Un in steps of 1%
Voltage Diff. 2 to 70% of Un in steps of 1%
Frequency Diff. 0.02 to 0.2 Hz in steps of 0.01Hz
Phase angle Diff 5º to 75º in steps of 1º
Dead Bus Voltage 30 to 80% of Un in steps of 1%
Time Delay 0.2 to 1.0 sec in steps of 0.1sec
DB/DL closing delay 2 to 20 sec in steps of 1 sec

Mechanical Design :

Weight 5000 gms. Approx.
Case Size 152X296 sq mm, depth 250mm
Installation Flush mounting
Panel cutout 146 x 264 mm

Standard Compliance :

Accuracy Test IEC 60255-3
Insulation Test IEC 60255-5

Accuracy:

Voltage ±5%
Frequency ±0.02Hz
Phase Angle ±2%
Operating time ±5%

Contact Ratings:

Trip / Alarm 10A at 24V DC / 230V AC

Contact Durability :

Loaded contact 10,000 operations minimum
Unloaded contact 100,000 operations minimum

Over Load Rating:

Voltage 1 & Voltage 2 200% of rated voltage (continuous) to both V1 & V2

Burden:

AC voltage input Less than 0.1VA at Un
Aux. Supply Less than 4W (Non Operated) Less than 8W (Operated)

Ordering Information

Relay type JNF 060
Voltage rating 110V or 63.5V
Aux. Supply 20 to 60V DC or
75 to 150V AC/ DC or
175 to 300V DC / 185 to 250V AC