Sai Creations

Numerical Over Current Relay with Communication JNC 068 CALP

 0.00

  • Programmable for 1A / 5A relay rating
  • Programmable system rated frequency (50/60Hz)
  • 3 OC + 1 EF + 1 SEF/REF
  • Available in both Low load and normal load configurations
  • Choice of 6 IDMT curves and definite time
  • Trip test facility
  • History of 6 latest faults along with settings
  • Self supervision facility
  • MODBUS open protocol over RS – 485 port
  • MODBUS protocol over RS – 232 port
  • Draw out facility with inbuilt CT shorting
  • Standard dimension – 144mm x 144mm

Principle of Operation:

The relay measures the line current from each of the line CTs and if the current exceeds the set threshold, then relay extends a trip signal after an operating time.

The relay’s “operating time” is determined by selecting “definite time” or one of the six “inverse time” characteristics.

Input to sensitive earth fault protection can be derived in two ways:

Residual current derived from three phase current transformers can be used as an input Out put of core balance current transformer (CBCT) having appropriate characteristics can be used as an input.

Input to high impedance restricted earth fault protection will be derived from neutral CT output with external stabilizing resistor.

Phase over current, Earth fault, Sensitive earth fault/Restricted earth fault protections features can be made active or inhibit independently. Inhibition of all protection is not possible

Application:

The relay provides time graded phase and earth fault (2 stage) protection with communication facility.

20 in stock

Description

Ratings

Current rating ( In ) 1A / 5A ( Site selectable)
Aux. Supply 1) 20 to 60V DC
2) 80 to 260V AC / DC

Settings:

Operating characteristics
(Separate for Phase &
Earth fault )
1) 3.0s Normal Inverse
2) 1.3s Normal Inverse
3) 1.5s Very Inverse
4) 0.8s Extremely Inverse
5) 0.6s Extremely Inverse
6) 13.3s Long Inverse
7) Definite Time
Phase OC (IDMT) 20 to 200% in steps of 5%
Phase OC (Def time) 50 to 500% in steps of 5 %
Earth fault (IDMT) 5 to 80% in steps of 1%
Earth fault (Def time) 5 to 100% in steps of 1%
SEF (Def time) 2 to 80% in steps of 1%
TMS (Ph & E/F) 0.02 to 1.0 in steps of 0.01
Definite time (Ph, E/F & SEF ) 0 to 25.0s in steps of 0.1s
(0 –Instantaneous)
Phase Hi-set 200 to 3200% in steps of 100%
Earth fault Hi-set 50 to 1000% in steps of 50%
Hi-set operating time
( Ph & E/F )
0 to 500ms in steps of 50ms
(0 – Instantaneous)
RS232 communication MODBUS Protocol 9-Pin
D at front end
RS485 communication MODBUS Protocol Isolated
Rs485 at rear end

Mechanical Design :

Weight 2.5 Kgs.(Approx)
Case Size Fascia 144mm x 144mmb depth 232mm
Installation Flush mounting
Panel cutout 138mm x 138mm

Accuracy:

Operating
value(IDMT)
105% to 125%
Operating value
(Def time)
100% to 115%
Hiset operating
value
±5%
Drop-off / pick-up Between 70% to 98%
Operating time ±5% or ±30ms whichever is higher, for 3.0s NI, 1.3s NI.±7% or ±30ms whichever is higher,
for 0.8s EI, 0.6s EI,1.5s VI & 13.3s LI characteristics.

Contact Ratings:

Trip Contact
Make & carry
1250VA at maximum 10A or 440V AC / 220V DC
Break capacity
Alarm, Self
2300VA at maximum 10A or 440V AC / 250V DC
supervision contacts 5A at 24V DC / 230V AC

Over Load Rating:

Current input 2 times rated continuous
20 times rated for 3s
40 times rated for 1s)

Burden:

Current input 0.4VA per phase (Rated 5A)
0.05VA per Phase (Rated 1A)
Aux. Supply Less than 8W (Non operated)
Less than 12W (Operated)

Reviews

There are no reviews yet.

Be the first to review “Numerical Over Current Relay with Communication JNC 068 CALP”

Your email address will not be published. Required fields are marked *

Get a Quick Quote