Features

  • Wide OC setting range
  • Wide time setting range
  • Fast reset time
  • High drop-off / pickup ratio

Principle of Operation:

If a fault occurs at the distribution end and the respective protective relay operates but the corresponding CB fails to operate then the system may have to face catastrophic consequences. JRC-154 is a instantaneous and definite time over current relay that also monitors the non-potential contacts of the downstream protective relays. The relay is designed to trip the feeder end CB if the protective relay at the distribution end operates but its corresponding CB fails to operate.

Application:

JRC 154 local breaker backup relay, is used to check the operation of distribution end circuit breakers and to trip the feeder end circuit breaker if the distribution end circuit breaker fails to trip.

20 in stock

Description

Ratings

Current rating ( In ) 1A / 5A
Frequency 50Hz
Aux. Supply 20 to 60V DC
75 to 175V AC / DC
175 to 300V DC
185 to 250V AC

Settings:

Over Current 5 to 200% in steps of 5%
Definite time 50 ms to 1.25 sec in steps of 10 ms.

Over Load Ratings:

AC current input 2 times rated continuous 20 times rated for 3 secs.

Burden:

AC current input 0.2VA Per phase (at Rated 5A) 0.05VA per Phase (at Rated 1A)
Aux. Supply Less than 5W (Non Operated) Less than 10W (Operated)

Operating Time

Instantaneous operating time Less than 10 ms.

Contact Ratings:

Rating 10A at 24V DC/230V AC

Contact Durability:

Unloaded contact 1,000,000 Operations
Loaded contact 100,000 Operations

Contact Durability :

Loaded contact 10,000 operations minimum
Unloaded contact 100,000 operations minimum

Insulation:

  1. 2KV RMS, 50 Hz for 1 minute / 2.5 KV for 1 sec Between all terminals and earth.
  2. 1 KV RMS, 50 Hz for 1 minute across open contacts as per IEC 60255-5

Mechanical Design :

Weight 2000 gms. (approx)
Case Size 144sq mm, depth 232mm
Installation Flush mounting
Panel cutout 138mm x 138mm

Standard Compliance:

Accuracy test IEC 60255-3
Insulation test IEC 60255-5

Ordering Information

Relay type JRC 154
Current rating 1A / 5A
Auxiliary Supply 1) 20 to 60V DC
2) 75 to 150V DC / AC
3) 175 to 300V DC / 185 to 250V AC