Sai Creations

JRV 922 Definite time under voltage relay 96 sq mm

 0.00

Features

  • Software based design
  • Instantaneous/Definite time selection
  • Wide auxiliary supply
  • Low burden

Principle of Operation:

JRV 922 provides under voltage protection for power systems. Relay operating time is determined by set definite time. The relay measures the voltage from input PT and if it exceeds the set threshold, it extends a trip signal after the operating time, which is determined by set definite time. The relay output contacts are self reset type. TEST button facilitates testing of relay contacts for trip and alarm circuits.

Application:

The relay provides under voltage protection of Motors, Generators, Capacitor Banks etc.

20 in stock

Description

Ratings

Voltage rating AC UVR 110V AC
DC UVR 110V DC
Auxiliary supply 20 to 60V DC
80 to 260V AC / DC

Settings:

Voltage setting 30 to 95% in steps of 5%
Definite time 0.1 to 25sec in steps of 0.1sec.

Over Load Rating:

Voltage input 2 times Rated continuous

Burden:

Voltage input Less than 2VA at Rated
Auxiliary supply Less than 3W (Non Operated) Less than 5W (Operated)

Accuracy:

Operating value ±5%
Operating time ± 5% or ± 20ms
Instantaneous Time Less than 40ms

Contact Ratings:

Contacts 1 & 2 5A at 24V DC / 230V AC

Mechanical Design :

Weight Appx. 500 gms
Case Size Fascia 96mm sq, depth of 105mm
Installation Flush mounting
Panel cutout 92mm x 92mm

Standard Compliance

Accuracy test IEC 60255-3
Insulation test IEC 60255-5

Contact Durability :

Unloaded contact 1,000,000 Operations.
Loaded contact 00,000 Operations

Ordering Information

Relay type JRV 922 (AC UVR)
JRV 922 (DC UVR)
Auxiliary supply 20 to 60V DC
80 to 260V AC / DC
Voltage rating AC UVR 110V AC
DC UVR 110V DC