Features
- Sensing by electronic circuit
- Low supervision current
- Immune to breaker operation
- Continuous monitoring
Principle of Operation:
TCSR monitors the healthiness of the trip circuit of breaker. Basically the circuit drives a small current through the breaker trip coil and monitors it continuously. If there is any failure in the trip circuit or trip coil circuit, the relay will sense and operate it’s output contacts. About 400ms delay is introduced to prevent false indication during circuit breaker operation. A test button is provided to test the relay contacts for trip and alarm in healthy condition only. The facility for monitoring two trip coils with independent power supply is provided in one enclosure.
Application:
Trip Circuit Supervision Relay (TCSR) is used formonitoring healthiness of the circuit breaker (CB) trip circuit, CB trip coil and CB power supply. The monitoring of two trip coil circuit has to be done by only one TCSR.