Principle of Operation:

The relay receives the fault initiation from the protection relay and that triggers the auto reclose function. After tripping the circuit breaker (CB), the Auto reclose function can reclose the CB. Normally , the first reclose (or shot) is so short in time that consumer cannot notice anything . However the fault is cleared and the feeder will continue in normal service. Even though the basic principle of Auto reclose is simple, there are a lot of different timers and parameters that have to be set.

Application:

The auto reclose function is normally used in feeder protection relays that are protecting an overhead line. Most of the overhead line faults are temporary in nature. Even 85% can be cleared by using the auto reclose function.

20 in stock

Description

Ratings

No. of shots 1shot or 2shot
Aux. Supply 1) 20 to 60V DC
2) 75 to 150V AC / DC
3) 175 to 300V DC
185 to 250V AC

Settings:

1 – Shot Reclaim time 5 – 80s in steps of 5s
Dead Time 3s – 10s in steps of 1s
2 -Shot Reclaim time 20 – 320s in steps of 20s
Dead Time 1 10s – 80s in steps of 10s
Dead Time 2 30s – 170s in steps of 20s

Over Load Rating:

Voltage input 120% of rated voltage continuously

Burden:

Aux. Supply Less than 5W (Non operated)
Less than 7W (Operated)

Accuracy:

Operating value ±5% or ±30ms whichever is higher

Contact Ratings:

Lockout Relay & Re close Relay 10A at 24V DC/ 230V AC

Contact Durability :

Unloaded contact 1,000,000 Operations.
Loaded contact 00,000 Operations

Insulation:

  1. 2KV RMS, 50 Hz for 1 minute / 2.5 KV for 1 s. Between all terminals and cases .
  2. 1KV RMS, 50 Hz for 1 minute across open contacts

Mechanical Design :

Weight 2500 gms. (approx)
Case Size Fascia 144sq mm, depth 117mm
Installation Flush mounting
Panel cutout 138×138 mm

Standard Compliance

Accuracy test IEC 60255-3
Insulation test IEC 60255-5

Ordering Information

Relay type JRV 144(1 shot )
JRV 144(2 shot )
Auxiliary 20 to 60V DC
75 to 150V AC / DC or
175 to 300V DC (185 to 250V AC)