Features
- Solid state reliability
- High speed operation
- Very high load impedance operation
Principle of Operation:
The relay consists of sensing the voltage across each of the fuses separately. In normal condition, the potential across the fuses is nearly zero. On opening out of the fuse the potential across the particular fuse goes up. This potential drives current through the LED of the opto-coupler. The opto-coupler gets switched on due to the current in the opto-coupler provides circuit path for external LED indication and as well for the electromagnetic relay. The sensing circuit comprising of the opto-coupler and the associated driving circuit is separate for each phase. However, the electromagnetic relay providing potential free contacts for alarm and control is common for all the 3 phases.
Application:
The relay monitors the healthiness of PT fuses.