Sai Creations

INVERSE TIME CURRENT RELAY JRC 068

 0.00

Features

  • Software based design
  • Programmable time current characteristics
  • Choice of four curves
  • Wide setting ranges
  • Draw – out case

Principle of Operation:

The relay measures the line current from each of the phases and if it exceeds the set threshold, then the relay extends a trip signal after an operating time. The relay’s operating time is determined by selecting one of the four inverse time characteristics. The relay has facility to active / inhibit the high set protection feature. The relay output contacts are self reset / Hand reset type. Relay operation without any fault current can be test facility.

Application:

The relay provides time graded phase and earth fault protection of Generators, Transformers, Feeder, capacitors etc.,

20 in stock

Description

Ratings

Current rating 1A / 5A
Auxiliary Supply 1) 20 to 60V DC
2) 75 to 175V AC / DC
3) 175 to 300V DC
185 to 250V AC

Settings:

Operating characteristics 1) 3.0s Normal Inverse
2) 1.3s Normal Inverse
3) 1.5s Very Inverse
4) 0.8s Extremely Inverse
5) 0.6s Extremely Inverse
Phase O/c (IDMT) 50 to 200% in steps of 10% or 20 to 140% in steps of 10%
Earth fault (IDMT) 5 to 80% in steps of 5%
TMS 0.1 to 1.0 in steps of 0.01 (separate for O/c & E/F)
Phase Hi-set 200 to 3200% in steps of 200%
Earth fault Hi-set 50 to 800% in steps of 50%

Burden:

Current input 0.2VA at Rated 5A
0.05VA at Rated 1A
Aux. Supply Less than 8W (Non operated)
Less than 10W (Operated)

Contact Ratings:

Trip / Alarm 10A at 24V DC / 230V AC

Over Load Rating:

Current input 2 times Rated continuous
20 times Rated for 3s
40 times Rated for 1s

Accuracy:

Operating value 105% to 120% of setting
Drop-off / pick-up Between 80% to 95%
Operating Time ±5% or ±30ms whichever is higher
High set operating value ±5% or ±30ms whichever is higher
High set operating time Less than 30ms @ 2 times current setting
Reset Time 160ms to 180ms

Contact Durability:

Unloaded contact 1,000,000 Operations
Loaded contact 100,000 Operations

Over Load Rating

Current input times rated continuous
20 times rated for 3s
40 times rated for 1s

Mechanical Design :

Weight 2500 gms. (approx)
Case Size Fascia 144sq mm, depth 232mm
Installation Flush mounting
Panel cutout 138mm x 138mm

Over Load Rating

Accuracy test IEC 60255-3
Insulation test IEC 60255-5

Ordering Information

Relay type JRC 068 (3O/c + E/F)
JRC 067 (3O/c + E/F)
JRC 066 (2O/c + E/F)
JRC 066P (3O/c)
JRC 064 (2O/c)
JRC 062 (E/F)
JRC 062P (1O/c)
JRC 054 (3O/c + E/F)
JRC 053 (2O/c + E/F)
JRC 053P (3O/c)
JRC 052 (2O/c)
JRC 051 (E/F)
JRC 051 (1O/c)
JRC 043 (3O/c)
JRC 043 (2O/c + E/F)
Current rating 1A or 5A
Reset type Self Reset or Hand Reset
Extremely Inverse Curve 0.8s EI or 0.6s EI
Auxiliary Supply 20 to 60V DC or
75 to 150V AC/ DC or
175 to 300V DC (185 to 250V AC)

Reviews

There are no reviews yet.

Be the first to review “INVERSE TIME CURRENT RELAY JRC 068”

Your email address will not be published. Required fields are marked *

Get a Quick Quote