feeder protection transformer backup protection corel nii series jnc 268

 0.00

Features

  • Suitable for 1A / 5A relay rating
  • Choice of 6 IDMT curve and definite time
  • History of 6 latest faults along with settings
  • Self supervision facility
  • Breaker status monitoring
  • In-built breaker trip circuit supervision
  • Disturbance records (DR) in IEEE COMTRADE
  • format – Optional
  • Event Records (ER) – Optional
  • Programmable digital inputs and outputs
  • MODBUS open protocol over RS – 485 port
  • MODBUS protocol over RS – 232 port
  • Draw out facility with inbuilt CT shorting

20 in stock

Description

Principle of Operation:

JNC 268 N / JNC 268 A / JNC 268 L : The relay measures the line current from each of the line CTs and if the current exceeds the set threshold, then relay extends a trip signal after an operating time. The relay’s “operating time” is determined by selecting “definite time” or one of the six “inverse time” characteristics.

A sensitive earth fault or restricted earth fault (suitable for high impedence REF scheme) is provided in the relay.The input to sensitive earth fault protection can be connected in two ways. First one the residual current derived from three phase current transformers, and second is low output core balance current transformer can be connected. The input to restricted earth fault protection will be derived from neutral CT output with external stabilizing resistor.The relay has facility to monitor circuit breaker operation through 52a or 52b aux contacts of circuit breaker.

4 programmable digital inputs (PDI) and 4 programmable digital outputs are provided and can be used to synthesize logic along with some internal digital inputs i.e.(phase OC pickup, Earth fault pickup, Phase high set trip, Earth fault OC trip, Earth fault high set trip,etc). Together, this feature can be effectively used to reduce the number of aux. tripping relays in a protection scheme. The trip relay (B1-B2) can be operated either when any one / more of the protection scheme provided inside JNC 268 x initiates the relay or any/more of the PDI initiates the same relay.

Each PDO has independent timer. Each PDI has programmable mask facility.The relay in-built breaker trip circuit supervision and dedicated alarm contact to indicate trip circuit failure.

JNC 268 A : Provides Multi shot auto re-closer facilitates automation of breaker operation. Auto re-closer can be programmed to provide a maximum of five shots. “Dead time” starts when a trip signal is provided due to the occurrence of a fault involving L-L or L-G or L-L-G or L-L-L or L-L-L-G. After an elapse of a time interval equal to “dead time”, closing command will be extended.

The “reclaim time” timer starts at the instant when the “dead time” timer expires. If after extending the “breaker close” signal an over current fault was detected before the “reclaim time” timer reached its terminal count, then the relay understands that the fault in the system is still persisting and the over current relay will issue a trip signal. The relay tries to close the breaker for a maximum of the programmed number of shots before it choses to lockout. The relay can be configured for independent trip sequence as IDMT or Def. time

JNC 268 L : The relay monitors line current even after the trip condition to ensure breaker operation. Even if small current exist in the line the relay sends trip command to adjacent or backup breaker after definite operating time. The current threshold and definite time required to detect breaker failure are programmable.

Application:

The relay provides time graded phase, earth fault (2 stage) protection along with 5 shot auto recloser and SCADA capability.

Ratings

Primary current rating 1A / 5A ( Site selectable)
Aux. Supply 1) 20 to 60V DC
2) 80 to 260V AC / DC
Aux. Supply 20 – 60V DC
75 – 150V AC /DC
175 – 300V DC or
185 – 250V AC

Settings:

Operating characteristics (Separate for Phase & Earth fault )
  • 3.0s Normal Inverse
  • 1.3s Normal Inverse
  • 1.5s Very Inverse
  • 0.8s Extremely Inverse
  • 0.6s Extremely Inverse
  • 13.3s Long Inverse
  • Definite Time
Phase OC (IDMT) 20 to 200% in steps of 5%
Phase OC (Def time) 20 to 500% in steps of 5%
Earth fault (IDMT) 5 to 80% in steps of 1%
Earth fault (Def time) 5 to 100% in steps of 1%
SEF (Def time) 1 to 16% in steps of 0.5%
REF (Instantaneous) 2 to 80% in steps of 1%
TMS (Ph & E/F) 0.02 to 1.0 in steps of 0.01
Definite time (Separate for Ph, E/F & SEF ) Instantaneous to 25.0s in steps of 0.1s
Phase High set 100 to 3200% in steps of 100%
Earth fault High set 50 to 1000% in steps of 50%
High set operating time ( Ph & E/F ) Instantaneous to 500ms in steps of 50ms
Breaker monitoring 1) 52a monitoring
2) 52b monitoring
3) None
RS232 communication MODBUS Protocol 9-Pin D at front end
RS485 communication MODBUS Protocol Isolated RS485 at rear end
No. of DR (optional) Two
Duration of DR 0.86s (0.46s Pre-fault and 0.4s Post-fault)
ER (optional) 120 events

JNC 268 A SETTINGS

Max. Shots (re-closing) Maximum of 5
Dead time 1 to 5 0.5 to 250s in steps of 0.1s
Reclaim time 10 to 250s in steps of 1s
Cold load pickup (CLP) 2 to 16 times the OC (IDMT)
CLP Delay 0.05s to 1.0s in steps of 0.01s

JNC 268 A SETTINGS :

Accuracy Test IEC 60255-3
Insulation Test IEC 60255-5

Mechanical Design :

Weight 2.5 Kgs.(Approx)
Case Size Fascia 144 sq. mm depth 232mm
Installation Flush mounting
Panel cutout 138mm x 138mm

Accuracy:

Operating value 105% to 125%
Operating value (Definite time) 100% to 115%
High set operating value ±5%
Drop-off / pick-up Between 70% to 98%
Operating time ±5% or ±30ms whichever is higher ±7% or ±30ms whichever is higher, for 0.8s EI, 1.5s VI & 13.3s LI characteristics.

Digital Input & Output

Potential Digital inputs 4 Nos ( 50 to 250V DC )
Non-Potential digital 4 NO contacts
outputs (5A at 24V DC / 230V AC)
Digital output timer Instantaneous to 25.0s in stepsof 0.1s

Contact Ratings:

Trip contact 1250VA at maximum 10A or
Make & carry 440V AC / 220V DC
Trip contact 2300VA at maximum 10A or
Break capacity 440V AC / 250V DC
Alarm contacts 10A at 24V DC / 230V AC

Contact Durability :

Electrical 100,000 operations min.
Mechanical 1000,000 operations min

Insulation

  1. 2 KV RMS, 50 Hz for 1 minute / 2.5 KV for 1 sec. Between all terminals and earth.
  2. 1KV RMS, 50 Hz for 1 minute across open contacts.

Over Load Rating:

Current input 2 times rated continuous
20 times rated for 3s
40 times rated for 1s

Burden:

Current input 0.4VA per phase (Rated 5A)
0.05VA per Phase (Rated 1A)
Aux. Supply Less than 8W (Non operated)
Less than 12W (Operated)

Ordering Information

Relay type JNC 268 X
N – No ARR and LBB
A – With ARR
L – With LBB
Aux. Supply 20 to 60V DC or
80 to 260V AC / DC
In-built protection element Sensitive earth fault or Restricted earth fault