JRV 402 Neutral earthing resistor monitoring relay

 0.00

Features

  • Solid state reliability
  • Built in Trip test facility
  • High sensitivity
  • Low burden

Principle of Operation:

A very low DC current is passed through the NER and this is monitored in the relay. If there is an open circuit in resistor or considerable change in the resistor value the same is detected in the monitoring circuit. After detecting the change, timer is shorted and output relay is deenergized at the end of internally set time delay ( 5 Sec ) The relay contact may be connected externally to Alarm/Trip circuit as required. Normally the output relay is kept energized. If there is a failure in Aux. Supply the output relay releases and extends the Alarm/Trip signal.

Application:

The relay is used to monitor the neutral earthing resistor.Transformer neutral is earthed through a resistance. This resistor is called as Neutral Earthing Resistor (NER). Neutral Earthing resistors are used to restrict the fault current through the transformer during earth fault conditions. The healthiness of NER is important as an open resistor would render earth leakage protection in operative and hazardous.

20 in stock

Description

Ratings

Auxiliary supply 230V, ±10%, 50Hz

Accuracy:

Operating value ± 0.5% or ± 20msec

Burden:

Aux. Supply Less than 5VA

Output Relay

Relay Two Changeover
Relay ratings 5A at 24V DC/230V AC, 50Hz.
Working voltage of the system for which relay is designed 565V, 3, 50Hz, with neutral resistance of435 ohms.
Tripping Level Resistance more than 150% of 435 ohms i.e., more than 653 ohms.

Contact Durability :

Unloaded contact 1,000,000 Operations.
Loaded contact 00,000 Operations

Insulation

  1. 2KV RMS, 50 Hz for 1 minute / 2.5 KV for 1 sec Between all terminals and cases .
  2. 1KV RMS, 50 Hz for 1 minute across open contacts

Mechanical Design :

Weight 1000gms. (approx
Case Size Fascia 83 x 148sq mm, depth 104mm
Installation Flush mounting
Panel cutout 73mm x 138mm

Contact Ratings:

Output Contacts 10A at 24V DC / 230V AC

Standard Compliance:

Accuracy test IEC 60255-3
Insulation test IEC 60255-5

Ordering Information

Relay type JRV 402
Aux. Supply 230V AC 50Hz